Can you use nicad batteries in a ups? Answered


Discussions

0
None
Slowpoke

Best Answer 8 years ago

I don't recommend it. 

Most UPSs use SLA (sealed lead acid) batteries and their charging circuits are designed to charge SLAs. There are big differences between charging NiCads and SLAs. If you were to just use NiCads in place of the SLA, the UPS will cook the NiCads very quickly. You would have to modify the charging circuit to correctly charge the NiCads.

Yes you can, but you need a UPS designed for the job.
So either - don't try it with the UPS you have, or do you really want to try making a UPS from scratch to go around the Ni-Cds you have?

L

No, I don't think I want to build one from scratch. Thank you for the reply.